HP LH4r HP Netserver LC 2000 Installation Guide - Page 169
Power Requirements
View all HP LH4r manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 169 highlights
A Specifications Power Requirements Table A-1. HP NetServer LC 2000/2000r Input Power Input Voltage and Frequency Maximum inrush current Delayed action circuit breaker recommended 100-240 VAC ± 10%; 50/60 Hz 8 AMPs peak (for 1 power supply) 120 VAC or 32 AMPs peak (2 power supplies) 16 AMPs peak (for 1 power supply) 240 VAC or 32 AMPs peak (2 power supplies) North America: a 20 A minimum delayed action circuit recommended for each 16 A power distribution unit (PDU) that is connected to an HP NetServer LC 2000/2000r. Europe (single server in a rack): use a 16 A-minimum circuit with one IEC MCB C-type breaker for each 16-Amp PDU. Europe (multiple servers in a rack): use a 16-amp-minimum circuit with one IEC MCB D-type breaker for each 16 A PDU. NOTE Some local codes do not allow 16-amp service for a 16-amp device. Consult a qualified electrician or local regulatory authority before beginning electrical site preparation. Table A-2. HP NetServer LC 2000/2000r Power Ratings AC Input Voltages Maximum Input Maximum Input Maximum Operating Power (VA) Power (W) Current RMS (AMPS) 100 VAC 545 540 5.5 120 VAC 531 525 4.5 208 VAC 516 506 2.5 230/240 VAC 514 504 2.3 161