Intel SR2400SYSD2 User Guide - Page 107

Installing or Replacing a Hot-swap Power Supply (AC Version), Removing a Hot-swap Power Supply

Page 107 highlights

Hardware Installations and Upgrades Installing or Replacing a Hot-swap Power Supply (AC Version) The power supply can be replaced if it, or one of the fans integrated into it, fails. If your server uses a redundant power supply, you do not need to power down your server to replace the failed power supply, as long as the remaining power supply is plugged into an AC power source and is functioning. If you do not have a redundant power supply installed, you must power down your server system before replacing the power supply. ✏ NOTE This procedure only applies to the AC version of the Intel® Server Chassis SR2400. If you are installing or replacing a hot swap power supply for the Intel® Server Chassis SR2400DC, see "Installing or Replacing a Hot-swap Power Supply (DC Version)" for instructions. Removing a Hot-swap Power Supply To replace the power supply, use the following instructions. 1. (Non-redundant power supply only) Power down the server. 2. Remove the AC power cable from the failed power supply. 3. Press the green latch at the rear of power supply and pull the power supply from the chassis. TP01119 Figure 75. Removing a Hot-swap Power Supply Intel® Server Chassis SR2400/SR2400DC User Guide 83

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124
  • 125
  • 126
  • 127
  • 128
  • 129
  • 130
  • 131
  • 132
  • 133
  • 134
  • 135
  • 136
  • 137
  • 138
  • 139

Hardware Installations and Upgrades
Intel® Server Chassis SR2400/SR2400DC User Guide
83
Installing or Replacing a Hot-swap Power Supply (AC
Version)
The power supply can be replaced if it, or one of the fans integrated into it, fails. If your server uses
a redundant power supply, you do not need to power down your server to replace the failed power
supply, as long as the remaining power supply is plugged into an AC power source and is
functioning. If you do not have a redundant power supply installed, you must power down your
server system before replacing the power supply.
NOTE
This procedure only applies to the AC version of the Intel® Server Chassis SR2400. If you are
installing or replacing a hot swap power supply for the Intel® Server Chassis SR2400DC, see
“Installing or Replacing a Hot-swap Power Supply (DC Version)” for instructions.
Removing a Hot-swap Power Supply
To replace the power supply, use the following instructions.
1.
(Non-redundant power supply only) Power down the server.
2.
Remove the AC power cable from the failed power supply.
3.
Press the green latch at the rear of power supply and pull the power supply from the chassis.
TP01119
Figure 75.
Removing a Hot-swap Power Supply