Dell PowerEdge T430 Dell PowerEdge T430 Owners Manual - Page 177
Environmental, Operating Altitude De-rating, Particulate Contamination, Gaseous Contamination - coupon
View all Dell PowerEdge T430 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 177 highlights
Environmental Operating Altitude De-rating Up to 35 °C (95 °F) Maximum temperature is reduced by 1 °C/300 m (1 °F/547 ft) above 950 m (3,117 ft). 35 °C to 40 °C (95 °F to 104 °F) Maximum temperature is reduced by 1 °C/175 m (1 °F/319 ft) above 950 m (3,117 ft). 40 °C to 45 °C (104 °F to 113 °F) Maximum temperature is reduced by 1 °C/125 m (1 °F/228 ft) above 950 m (3,117 ft). Particulate Contamination NOTE: This section defines the limits to help avoid IT equipment damage and/or failure from particulates and gaseous contamination. If it is determined that levels of particulates or gaseous pollution are beyond the limits specified below and are the reason for the damage and/or failures to your equipment, it may be necessary for you to re-mediate the environmental conditions that are causing the damage and/or failures. Re-mediation of environmental conditions will be the responsibility of the customer. Air Filtration Data center air filtration as defined by ISO Class NOTE: Applies to data center environments only. Air filtration requirements do not apply 8 per ISO 14644-1 with a 95% upper confidence limit. to IT equipment designed to be used outside NOTE: Air entering the data center must a data center, in environments such as an have MERV11 or MERV13 filtration. office or factory floor. Conductive Dust NOTE: Applies to data center and non-data center environments. Air must be free of conductive dust, zinc whiskers, or other conductive particles. Corrosive Dust NOTE: Applies to data center and non-data center environments. • Air must be free of corrosive dust. • Residual dust present in the air must have a deliquescent point less than 60% relative humidity. Gaseous Contamination NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity. Copper Coupon Corrosion Rate Silver Coupon Corrosion Rate