HP Integrity rx2800 HP Insight Management WBEM Provider Events Reference Guide - Page 47

Bulk Power Supplies are not Redundant. Probable Cause: Entities were added to

Page 47 highlights

7796 7798 7799 7803 7806 7822 7823 7824 7825 7827 7828 7829 Warning Warning Error Error Warning Error Error Warning Warning Error Warning Error 1 Side Converter Over Temp. Probable Cause: If there are chassis codes indicating an elevated ambient air temperature, other chassis codes will be generated and system shutdown will be necessary. Recommended Action: Resolve the elevated ambient air temperature problem as quickly as possible. If the air temperature gets too high, the complex must be shutdown to avoid damage. WBEM EventID: 2436. WBEM ProviderName: FPL_IndicationProvider. Bulk Power Supplies are not Redundant. Probable Cause: Entities were added to the cabinet, increasing the estimated Power Consumption. Or, a non-functional GSP bus entity has become functional, providing previously missing power consumption information. Recommended Action: Purchase and install a Bulk Power Supply, if redundancy is desired. WBEM EventID: 659. WBEM ProviderName: FPL_IndicationProvider. +48V DC has exceeded its upper limit. Probable Cause: The cabinet's 48V power has exceeded an acceptable upper threshold. Recommended Action: Contact HP Support personnel to troubleshoot problem. WBEM EventID: 660. WBEM ProviderName: FPL_IndicationProv +48V DC has fallen below its lower limit. Probable Cause: The cabinet's 48V power has fallen below an acceptable lower threshold. Recommended Action: Contact HP Support personnel to troubleshoot problem. WBEM EventID: 661. WBEM ProviderName: FPL_Indica Cabinet Fan Failed. Probable Cause: Cabinet Fan Failed. Recommended Action: Replace failed cabinet fan module as soon as possible following the Cabinet Fan Module Remove and Replace Procedures. WBEM EventID: 662. WBEM ProviderName: FPL_IndicationProvider. Housekeeping power has exceeded expected levels. Probable Cause: The cabinet's housekeeping power has risen above an acceptable upper threshold. Recommended Action: Contact HP Support personnel to troubleshoot problem. WBEM EventID: 670. WBEM ProviderName: FPL_IndicationProvider. Housekeeping power has fallen below expected levels. Probable Cause: The cabinet's housekeeping power has fallen below an acceptable upper threshold. Recommended Action: Contact HP Support personnel to troubleshoot problem. WBEM EventID: 671. WBEM ProviderName: FPL_IndicationProvider. The BPSs for the cabinet are illegally configured. Data Byte 3 = PDCA number. Probable Cause: The BPS are installed in an illegal configuration. Recommended Action: Re-configure the BPS in a manner consistent with the explanation in the Problem Description statement. WBEM EventID: 672. WBEM ProviderName: FPL_IndicationProvider. BPS ID received from installed Bulk Power Supply was unknown. Probable Cause: A new revision of Power Supply that requires a PM3 firmware upgrade was attempting install. Recommended Action: Check service notes for firmware revisions and compatibility charts. WBEM EventID: 673. WBEM ProviderName: FPL_IndicationProvider. Ambient Air Sensor Overtemp Warning. Probable Cause: Room Temperature has risen to a critical level. Recommended Action: Shutdown and power off the system. Correct air temperature problem. WBEM EventID: 675. WBEM ProviderName: FPL_IndicationProvider. Ambient Air Sensor Overtemp Warning. Probable Cause: Room Temperature is rising or falling. Recommended Action: Check the error log's previous entries within a logical time frame. If temperature is rising, prepare for system shutdown. If temperature is dropping, then problem is probably resolved. WBEM EventID: 676. WBEM ProviderName: FPL_IndicationProvider. Ambient Air Sensor Overtemp Warning. Probable Cause: Room Temperature is rising or falling. Recommended Action: Check the error log's previous entries within a logical time frame. If temperature is rising, prepare for system shutdown. If temperature is dropping, then problem is probably resolved. WBEM EventID: 677. WBEM ProviderName: FPL_IndicationProvider. Platform Events 47

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112

1 Side Converter Over Temp. Probable Cause: If there are chassis codes indicating
an elevated ambient air temperature, other chassis codes will be generated and system
shutdown will be necessary. Recommended Action: Resolve the elevated ambient
air temperature problem as quickly as possible. If the air temperature gets too high,
the complex must be shutdown to avoid damage. WBEM EventID: 2436. WBEM
ProviderName: FPL_IndicationProvider.
Warning
7796
Bulk Power Supplies are not Redundant. Probable Cause: Entities were added to the
cabinet, increasing the estimated Power Consumption. Or, a non-functional GSP bus
entity has become functional, providing previously missing power consumption
information. Recommended Action: Purchase and install a Bulk Power Supply, if
redundancy is desired. WBEM EventID: 659. WBEM ProviderName:
FPL_IndicationProvider.
Warning
7798
+48V DC has exceeded its upper limit. Probable Cause: The cabinet's 48V power has
exceeded an acceptable upper threshold. Recommended Action: Contact HP Support
personnel to troubleshoot problem. WBEM EventID: 660. WBEM ProviderName:
FPL_IndicationProv
Error
7799
+48V DC has fallen below its lower limit. Probable Cause: The cabinet's 48V power
has fallen below an acceptable lower threshold. Recommended Action: Contact HP
Support personnel to troubleshoot problem. WBEM EventID: 661. WBEM
ProviderName: FPL_Indica
Error
7803
Cabinet Fan Failed. Probable Cause: Cabinet Fan Failed. Recommended Action:
Replace failed cabinet fan module as soon as possible following the Cabinet Fan
Module Remove and Replace Procedures. WBEM EventID: 662. WBEM ProviderName:
FPL_IndicationProvider.
Warning
7806
Housekeeping power has exceeded expected levels. Probable Cause: The cabinet's
housekeeping power has risen above an acceptable upper threshold. Recommended
Action: Contact HP Support personnel to troubleshoot problem. WBEM EventID:
670. WBEM ProviderName: FPL_IndicationProvider.
Error
7822
Housekeeping power has fallen below expected levels. Probable Cause: The cabinet's
housekeeping power has fallen below an acceptable upper threshold. Recommended
Action: Contact HP Support personnel to troubleshoot problem. WBEM EventID:
671. WBEM ProviderName: FPL_IndicationProvider.
Error
7823
The BPSs for the cabinet are illegally configured. Data Byte 3 = PDCA number.
Probable Cause: The BPS are installed in an illegal configuration. Recommended
Action: Re-configure the BPS in a manner consistent with the explanation in the
Problem Description statement. WBEM EventID: 672. WBEM ProviderName:
FPL_IndicationProvider.
Warning
7824
BPS ID received from installed Bulk Power Supply was unknown. Probable Cause:
A new revision of Power Supply that requires a PM3 firmware upgrade was
attempting install. Recommended Action: Check service notes for firmware revisions
and compatibility charts. WBEM EventID: 673. WBEM ProviderName:
FPL_IndicationProvider.
Warning
7825
Ambient Air Sensor Overtemp Warning. Probable Cause: Room Temperature has
risen to a critical level. Recommended Action: Shutdown and power off the system.
Correct air temperature problem. WBEM EventID: 675. WBEM ProviderName:
FPL_IndicationProvider.
Error
7827
Ambient Air Sensor Overtemp Warning. Probable Cause: Room Temperature is
rising or falling. Recommended Action: Check the error log's previous entries within
a logical time frame. If temperature is rising, prepare for system shutdown. If
temperature is dropping, then problem is probably resolved. WBEM EventID: 676.
WBEM ProviderName: FPL_IndicationProvider.
Warning
7828
Ambient Air Sensor Overtemp Warning. Probable Cause: Room Temperature is
rising or falling. Recommended Action: Check the error log's previous entries within
a logical time frame. If temperature is rising, prepare for system shutdown. If
temperature is dropping, then problem is probably resolved. WBEM EventID: 677.
WBEM ProviderName: FPL_IndicationProvider.
Error
7829