HP LH4r HP Netserver LXr 8500 Installation Guide - Page 175
Power Requirements
View all HP LH4r manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 175 highlights
A Specifications Power Requirements Table A-1. Power Requirements Voltage and frequency Maximum continuous power input Operating Current Maximum inrush current Delayed action circuit breaker recommended Power availability 200-240 VAC; 50/60 Hz 1100 W Maximum (8-CPU configuration) 5.6 AMPs Maximum at 200/208 Volts AC 4.9 AMPs Maximum at 230/240 Volts AC 150 AMPs for 4 ms North America: a 20 A minimum circuit is to be used with one NEMA AB1 class 14B breaker for each 16 A power distribution unit (PDU) that is connected to an HP NetServer LXr 8500. Europe (single server in a rack): use a 16 A-minimum circuit with one IEC MCB C-type breaker for each 16 AMP PDU. Europe (multiple servers in a rack): use a 16-amp-minimum circuit with one IEC MCB D-type breaker for each 16 AMP PDU. 1500 DC watts continuous (2 power supplies minimum) NOTE Some local codes do allow a 16-amp device to be connected to a 16-amp service. Consult a qualified electrician or local regulatory authority before beginning electrical site preparation. 167