Event ID Event Severity 7825 Warning 7827 Error 7828 Warning 7829 Error 7836 Warning 7842 Warning 7845 Error 7846 Error 7849 Warning 7855 Error 7856 Error Event Description BPS ID received from installed Bulk Power Supply was unknown. Probable Cause: The designated power supply is responding with an illegal BPS ID. It could be a faulty supply, a different revision, or a wrong supply in the wrong box. Recommended Action: Replace this Bulk Power Supply with a proper one. WBEM EventID: 673. WBEM ProviderName: FPL_IndicationProvider. Ambient Air Sensor Overtemp Warning. Probable Cause: Room Temperature has risen to a critical level. Recommended Action: Shutdown and power off the system. Correct air temperature problem. WBEM EventID: 675. WBEM ProviderName: FPL_IndicationProvider. Ambient Air Sensor Overtemp Warning. Probable Cause: Room Temperature is rising or falling. Recommended Action: Check the error log's previous entries within a logical time frame. If temperature is rising, prepare for system shutdown. If temperature is dropping, then problem is probably resolved. WBEM EventID: 676. WBEM ProviderName: FPL_IndicationProvider. Ambient Air Sensor Overtemp Warning. Probable Cause: Room Temperature is rising or falling. Recommended Action: Check the error log's previous entries within a logical time frame. If temperature is rising, prepare for system shutdown. If temperature is dropping, then problem is probably resolved. WBEM EventID: 677. WBEM ProviderName: FPL_IndicationProvider. IO Fan Failed. Probable Cause: IO Cooling Fan Failed Recommended Action: Replace IO Fan Module as soon as possible following the IO Fan Module Remove and Replace Procedures. WBEM EventID: 678. WBEM ProviderName: FPL_IndicationProvider. Cabinet Power System is in overload. Probable Cause: A Bulk Power Supply has failed, or, entities were added. Look for one or more BPS_Fail Chassis Codes preceding this one for the actual failures. This code is a warning of possible cabinet unreliability. Recommended Action: Contact HP Support personnel to troubleshoot the problem. WBEM EventID: 680. WBEM ProviderName: FPL_IndicationProvider. Cabinet Shutdown - Insufficient Blowers. Probable Cause: One blower has failed creating condition N. Before condition N was corrected, another blower in the same cabinet was declared failed. This created the illegal condition of N-1. Recommended Action: Contact HP Support personnel to troubleshoot the problem. WBEM EventID: 681. WBEM ProviderName: FPL_IndicationProvider. Cabinet Shutdown - Insufficient IO Fans. Probable Cause: One IO fan has failed creating condition N. Before condition N was corrected, another IO fan in the same cabinet failed. This created the illegal condition of N-1. Recommended Action: Contact HP Support personnel to troubleshoot the problem. WBEM EventID: 682. WBEM ProviderName: FPL_IndicationProvider. IO Expansion Utility Cabinet Fan Failed. Probable Cause: IO Expansion Utility Fan or Fan sensor failure PM failure Recommended Action: Contact HP Support personnel to troubleshoot the problem. WBEM EventID: 683. WBEM ProviderName: FPL_IndicationProvider. Watchdog Timer Expired. Probable Cause: CLU has been reset after a firmware update. Recommended Action: No action is required. WBEM EventID: 684. WBEM ProviderName: FPL_IndicationProvider. Invalid checksum from EEPROM. Probable Cause: Problem with I2C bus. Recommended Action: If every entity with a FRUID logs an error, the problem is probably with the CLU portion of the Utilities Board. Replace the Utilities Board following the Utilities Board Remove and Replace Procedures. If there are a few entities reporting checksum errors, but several have reported in properly, chances are one device is causing the problem with the I2C bus. This will take a more concerted effort to find and correct that problem. Probably wish to take the bus to a minimum configuration and test, add, test until the failure is verified. WBEM EventID: 685. WBEM ProviderName: FPL_IndicationProvider. 44 WBEM Provider Event Tables

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112

Event Description
Event
Severity
Event ID
BPS ID received from installed Bulk Power Supply was unknown. Probable Cause:
The designated power supply is responding with an illegal BPS ID. It could be a
faulty supply, a different revision, or a wrong supply in the wrong box. Recommended
Action: Replace this Bulk Power Supply with a proper one. WBEM EventID: 673.
WBEM ProviderName: FPL_IndicationProvider.
Warning
7825
Ambient Air Sensor Overtemp Warning. Probable Cause: Room Temperature has
risen to a critical level. Recommended Action: Shutdown and power off the system.
Correct air temperature problem. WBEM EventID: 675. WBEM ProviderName:
FPL_IndicationProvider.
Error
7827
Ambient Air Sensor Overtemp Warning. Probable Cause: Room Temperature is
rising or falling. Recommended Action: Check the error log's previous entries within
a logical time frame. If temperature is rising, prepare for system shutdown. If
temperature is dropping, then problem is probably resolved. WBEM EventID: 676.
WBEM ProviderName: FPL_IndicationProvider.
Warning
7828
Ambient Air Sensor Overtemp Warning. Probable Cause: Room Temperature is
rising or falling. Recommended Action: Check the error log's previous entries within
a logical time frame. If temperature is rising, prepare for system shutdown. If
temperature is dropping, then problem is probably resolved. WBEM EventID: 677.
WBEM ProviderName: FPL_IndicationProvider.
Error
7829
IO Fan Failed. Probable Cause: IO Cooling Fan Failed Recommended Action: Replace
IO Fan Module as soon as possible following the IO Fan Module Remove and Replace
Procedures. WBEM EventID: 678. WBEM ProviderName: FPL_IndicationProvider.
Warning
7836
Cabinet Power System is in overload. Probable Cause: A Bulk Power Supply has
failed, or, entities were added. Look for one or more BPS_Fail Chassis Codes preceding
this one for the actual failures. This code is a warning of possible cabinet unreliability.
Recommended Action: Contact HP Support personnel to troubleshoot the problem.
WBEM EventID: 680. WBEM ProviderName: FPL_IndicationProvider.
Warning
7842
Cabinet Shutdown - Insufficient Blowers. Probable Cause: One blower has failed
creating condition N. Before condition N was corrected, another blower in the same
cabinet was declared failed. This created the illegal condition of N-1. Recommended
Action: Contact HP Support personnel to troubleshoot the problem. WBEM EventID:
681. WBEM ProviderName: FPL_IndicationProvider.
Error
7845
Cabinet Shutdown - Insufficient IO Fans. Probable Cause: One IO fan has failed
creating condition N. Before condition N was corrected, another IO fan in the same
cabinet failed. This created the illegal condition of N-1. Recommended Action: Contact
HP Support personnel to troubleshoot the problem. WBEM EventID: 682. WBEM
ProviderName: FPL_IndicationProvider.
Error
7846
IO Expansion Utility Cabinet Fan Failed. Probable Cause: IO Expansion Utility Fan
or Fan sensor failure PM failure Recommended Action: Contact HP Support personnel
to troubleshoot the problem. WBEM EventID: 683. WBEM ProviderName:
FPL_IndicationProvider.
Warning
7849
Watchdog Timer Expired. Probable Cause: CLU has been reset after a firmware
update. Recommended Action: No action is required. WBEM EventID: 684. WBEM
ProviderName: FPL_IndicationProvider.
Error
7855
Invalid checksum from EEPROM. Probable Cause: Problem with I2C bus.
Recommended Action: If every entity with a FRUID logs an error, the problem is
probably with the CLU portion of the Utilities Board. Replace the Utilities Board
following the Utilities Board Remove and Replace Procedures. If there are a few
entities reporting checksum errors, but several have reported in properly, chances
are one device is causing the problem with the I2C bus. This will take a more concerted
effort to find and correct that problem. Probably wish to take the bus to a minimum
configuration and test, add, test until the failure is verified. WBEM EventID: 685.
WBEM ProviderName: FPL_IndicationProvider.
Error
7856