HP Integrity Superdome SX2000 HP Insight Manager WBEM Provider Events Referenc - Page 48

of one or more Cell Board or Cell Power Board converters. WBEM EventID: 625.

Page 48 highlights

Event ID Event Severity 7974 Error 7975 Error 8009 Error 8010 Warning 8127 Error 8128 Error 8130 Warning 8131 Warning 8132 Warning 8133 Warning 8134 Warning 8135 Warning 8136 Warning Event Description Firmware encountered an error in processing the partition variables. Probable Cause: Either the GSP was not present or there was a resource problem storing the variable. There should be other clues in the event id log to indicate which is the case. Restore the GSP. WBEM EventID: 619. WBEM ProviderName: FPL_IndicationProvider. A non-critical cell power fault has occurred. Probable Cause: A power converter has failed. Recommended Action: Contact HP Support personnel to troubleshoot the problem. WBEM EventID: 620. WBEM ProviderName: FPL_IndicationProvider. CPUProcConfigValue in /options is not compatible with the current PAL/CPU. Probable Cause: Modify CPUProcConfigValue in /options to set the correct bits. WBEM EventID: 2439. WBEM ProviderName: FPL_IndicationProvider. Firmware was unable to determine the Processor Dependent Features. Probable Cause: Contact Engineering, This is a bug. WBEM EventID: 622. WBEM ProviderName: FPL_IndicationProvider. Data field contains data meant for firmware debug only. Probable Cause: Debug event. Recommended Action: Contact your hp support representative. WBEM EventID: 2434. WBEM ProviderName: FPL_IndicationProvider. The CLU has encountered an undefined case. Probable Cause: CLU firmware on the UGUY has gotten into an unexpected execution path, most likely due to a hardware issue on the UGUY. Recommended Action: Check revision of CLU firmware. If out of date, or known bad revision, use FWUU to update CLU firmware. Contact HP Support personnel to troubleshoot problem. WBEM EventID: 624. WBEM ProviderName: FPL_IndicationProvider. An unknown Cell voltage margin has been detected. Probable Cause: A user has manually, using back-door debugging methods, altered the voltage margin setting of one or more Cell Board or Cell Power Board converters. WBEM EventID: 625. WBEM ProviderName: FPL_IndicationProvider. The run-time verification of a programming assumption has failed. Probable Cause: Hardware or software in unknown state. Recommended Action: Upgrade PDHC firmware to latest revision. If already at current revision, contact HP Support personnel to troubleshoot the problem. WBEM EventID: 626. WBEM ProviderName: FPL_IndicationProvider. An unknown error has been detected by the PDHC firmware. Probable Cause: Hardware in unknown state, or programming bug found. Recommended Action: Recommended Action: Upgrade PDHC firmware to latest revision. If already at current revision, contact HP support personnel to troubleshoot the problem. WBEM EventID: 627. WBEM ProviderName: FPL_IndicationProvider. An attempt to write to a device on the PDHCs I2C bus has failed. Probable Cause: A hardware fault has occurred. Recommended Action: Contact HP Support personnel to troubleshoot the Cell Board, Cell Power Board, and/or PDH Daughtercard. WBEM EventID: 628. WBEM ProviderName: FPL_IndicationProvider. An attempt to read from a device on the PDHC's I2C bus has failed. Probable Cause: A hardware fault has occurred. Recommended Action: Contact HP Support personnel to troubleshoot the Cell Board, Cell Power Board, and/or PDH Daughtercard. WBEM EventID: 629. WBEM ProviderName: FPL_IndicationProvider. An attempt to write to a device on the PDHC's SM bus has failed. Probable Cause: A hardware fault has occurred. Recommended Action: Contact HP Support personnel to troubleshoot the Cell Board, Cell Power Board, and/or PDH Daughtercard. WBEM EventID: 630. WBEM ProviderName: FPL_IndicationProvider. An attempt to read from a device on the PDHC's SM bus has failed. Probable Cause: A hardware fault has occurred. Recommended Action: Contact HP Support personnel to troubleshoot the Cell Board, Cell Power Board, and PDH Daughtercard. WBEM EventID: 631. WBEM ProviderName: FPL_IndicationProvider. 48 WBEM Provider Event Tables

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112

Event Description
Event
Severity
Event ID
Firmware encountered an error in processing the partition variables. Probable Cause:
Either the GSP was not present or there was a resource problem storing the variable.
There should be other clues in the event id log to indicate which is the case. Restore
the GSP. WBEM EventID: 619. WBEM ProviderName: FPL_IndicationProvider.
Error
7974
A non-critical cell power fault has occurred. Probable Cause: A power converter has
failed. Recommended Action: Contact HP Support personnel to troubleshoot the
problem. WBEM EventID: 620. WBEM ProviderName: FPL_IndicationProvider.
Error
7975
CPUProcConfigValue in /options is not compatible with the current PAL/CPU.
Probable Cause: Modify CPUProcConfigValue in /options to set the correct bits.
WBEM EventID: 2439. WBEM ProviderName: FPL_IndicationProvider.
Error
8009
Firmware was unable to determine the Processor Dependent Features. Probable
Cause: Contact Engineering, This is a bug. WBEM EventID: 622. WBEM
ProviderName: FPL_IndicationProvider.
Warning
8010
Data field contains data meant for firmware debug only. Probable Cause: Debug
event. Recommended Action: Contact your hp support representative. WBEM
EventID: 2434. WBEM ProviderName: FPL_IndicationProvider.
Error
8127
The CLU has encountered an undefined case. Probable Cause: CLU firmware on the
UGUY has gotten into an unexpected execution path, most likely due to a hardware
issue on the UGUY. Recommended Action: Check revision of CLU firmware. If out
of date, or known bad revision, use FWUU to update CLU firmware. Contact HP
Support personnel to troubleshoot problem. WBEM EventID: 624. WBEM
ProviderName: FPL_IndicationProvider.
Error
8128
An unknown Cell voltage margin has been detected. Probable Cause: A user has
manually, using back-door debugging methods, altered the voltage margin setting
of one or more Cell Board or Cell Power Board converters. WBEM EventID: 625.
WBEM ProviderName: FPL_IndicationProvider.
Warning
8130
The run-time verification of a programming assumption has failed. Probable Cause:
Hardware or software in unknown state. Recommended Action: Upgrade PDHC
firmware to latest revision. If already at current revision, contact HP Support
personnel to troubleshoot the problem. WBEM EventID: 626. WBEM ProviderName:
FPL_IndicationProvider.
Warning
8131
An unknown error has been detected by the PDHC firmware. Probable Cause:
Hardware in unknown state, or programming bug found. Recommended Action:
Recommended Action: Upgrade PDHC firmware to latest revision. If already at
current revision, contact HP support personnel to troubleshoot the problem. WBEM
EventID: 627. WBEM ProviderName: FPL_IndicationProvider.
Warning
8132
An attempt to write to a device on the PDHCs I2C bus has failed. Probable Cause:
A hardware fault has occurred. Recommended Action: Contact HP Support personnel
to troubleshoot the Cell Board, Cell Power Board, and/or PDH Daughtercard. WBEM
EventID: 628. WBEM ProviderName: FPL_IndicationProvider.
Warning
8133
An attempt to read from a device on the PDHC's I2C bus has failed. Probable Cause:
A hardware fault has occurred. Recommended Action: Contact HP Support personnel
to troubleshoot the Cell Board, Cell Power Board, and/or PDH Daughtercard. WBEM
EventID: 629. WBEM ProviderName: FPL_IndicationProvider.
Warning
8134
An attempt to write to a device on the PDHC's SM bus has failed. Probable Cause:
A hardware fault has occurred. Recommended Action: Contact HP Support personnel
to troubleshoot the Cell Board, Cell Power Board, and/or PDH Daughtercard. WBEM
EventID: 630. WBEM ProviderName: FPL_IndicationProvider.
Warning
8135
An attempt to read from a device on the PDHC's SM bus has failed. Probable Cause:
A hardware fault has occurred. Recommended Action: Contact HP Support personnel
to troubleshoot the Cell Board, Cell Power Board, and PDH Daughtercard. WBEM
EventID: 631. WBEM ProviderName: FPL_IndicationProvider.
Warning
8136
48
WBEM Provider Event Tables