Dell PowerEdge XE2420 EMC Installation and Service Manual - Page 160
Environmental specifications, Operational climatic range category A2
View all Dell PowerEdge XE2420 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 160 highlights
Table 60. Supported front video resolution options (continued) Resolution Refresh rate (Hz) 1680 x 1050 (WSXGA+) 60 1280 x 1024 (SXGA) 60 1440 x 900 (WXGA+) 60 1920 x 1080 (FHD) 60 1280 x 800 (WXGA) 60 Environmental specifications NOTE: For additional information about environmental certifications, see the Product Environmental Datasheet located with the Manuals and Documents on https://www.dell.com/support. Operational climatic range category A2 Table 61. Operational climatic range category A2 Allowable continuous operations Temperature ranges for altitude
Table 60. Supported front video resolution options (continued)
Resolution
Refresh rate (Hz)
1680 x 1050 (WSXGA+)
60
1280 x 1024 (SXGA)
60
1440 x 900 (WXGA+)
60
1920 x 1080 (FHD)
60
1280 x 800 (WXGA)
60
Environmental specifications
NOTE:
For additional information about environmental certifications, see the
Product Environmental Datasheet
located
with the Manuals and Documents on
.
Operational climatic range category A2
Table 61. Operational climatic range category A2
Allowable continuous operations
Temperature ranges for altitude
<900 meters (
<2,953 ft.
10°C–35°C (50°F–95°F) with no direct sunlight on the
platform
Humidity percent ranges (Noncondensing always)
8% RH with -12°C minimum dew hover over 80% RH with
21°C (69.8°F) maximum dew point
Operational altitude derating
Maximum temperature is reduced by 1°C/300 meters
(1.8°F/984 ft) above 900 meters (2,953 ft)
Operational climatic range category A3
Table 62. Operational climatic range category A3
Allowable continuous operations
Temperature ranges for altitude
<900 meters (
<2,953 ft)
5°C–40°C (41°F–104°F) with no direct sunlight on the
platform
Humidity percent ranges (Noncondensing always)
8% RH with -12°C minimum dew hover over 85% RH with
24°C (75.2°F) maximum dew point
Operational altitude derating
Maximum temperature is reduced by 1°C/175 meters
(1.8°F/574 ft) above 900 meters (2,953 feet)
Thermal restriction for ASHRAE A3/Environment
●
CPU TDP greater than 150 W are not supported.
160
Technical specifications