Dell PowerVault NX3500 Administrator's Guide - Page 194
Table A-1., External Alarm Conditions, Alarm, Description, Audible, Corrective Action, BPS Alarms
View all Dell PowerVault NX3500 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 194 highlights
Table A-1. External Alarm Conditions (continued) Alarm Description Audible Site wiring problem Site Fault detection is Beeping supported on LV & HV models anytime there is a Neutral connection AND it is an LV model or has been manually enabled on the HV model. Alarm triggers when the difference between ground and neutral voltage is >= 25Vrms. Output Load greater than level Beeping overload level 2 threshold and less L2 than level 3 threshold. Alarm clears when the load drops below 5% of the set point. Output overload level L3 Load greater than level 3 threshold. Alarm clears when the load drops below 5% of the set point. Beeping Battery DC over voltage Battery voltage levels have exceeded the maximum allowable limits. Beeping Inverter AC over voltage UPS has detected abnormally high inverter output voltage levels. Beeping Inverter AC UPS has detected Beeping under voltage abnormally low inverter output voltage levels Corrective Action Check the site wiring. Contact Dell. Contact Dell. Contact Dell. Contact Dell. Contact Dell. 194 BPS Alarms